Ari Series_AP-PRO 500VA-3000VA

Features

  • Pure sine wave output
  • Output power factor 0.8
  • DSP digital control
  • Boost and buck AVR for voltage stabilization
  • Auto sensing frequency
  • Adjustable charging current and battery shutdown point
  • Settable ECO mode and no-load shutdown
  • Humanized alarm system
  • Power-on self test
  • Cold start
  • Auto restart when mains power is restored
  • Intelligent battery management
  • Short circuit and overload protection
  • Automatic charging in OFF mode
  • USB & RJ45, AS400/SNMP (optional) communication port

Technical Specification

 

Model AP500-PRO AP1000-PRO AP1500-PRO AP2000-PRO AP3000-PRO
Capacity 500VA/300W 1000VA/800W 1500VA/1200W 2000VA/1600W 3000VA/2400W
Rated Voltage 12V 24V 36V(S) 48V(H) 48V
DC input range 10-15V 20-30V 30-45V(S) 40-60V(H) 40-60V
AC INPUT          

AC Input range

(bypass mode)

0-121V / 132V / 138V / 144VAC for 100V / 110V / 115V / 120VAC ± 10VAC

0-242V / 264V / 276V / 288 VAC for 200V / 220V / 230V / 240VAC ± 10VAC

AC input range

(mains mode)

100V: 70 - 130VAC 110V: 80-140VAC 115V:85-145VAC 120V:90-150VAC

200V: 145-260VAC 220V:165-280VAC 230V:175-290VAC 240V:185-300VAC

Frequency input range 50Hz/60Hz (auto-sense), 50Hz/60Hz ± 5% - 15%
Generator connection Available (generator input power is settable)
OUTPUT          
Inverter output range 100V / 110V / 115V / 120V / 200V / 220V / 230V / 240VAC ± 5% (settable)

AC output range

(bypass mode)

0-121V / 132V / 138V / 144VAC for 100V / 110V / 115V / 120VAC ± 10VAC

0-242V / 264V / 276V / 288 VAC for 200V / 220V / 230V / 240VAC ± 10VAC

AC output range

(mains mode)

100V:90-110VAC 110V:99-121VAC 115V: 103-126VAC 120V:108-132VAC

200V: 166-226VAC 220V: 188-245VAC 230V: 199-254VAC 240V: 210-264VAC

Output frequency 50/60Hz ± 0.3 Hz (settable)
Waveform Pure sine wave
Inverter efficiency Max. 75% Max. 80% Max. 85%
Energy saving mode Settable (<3% load), enter in 80s
No-load shutdown Settable (<3% load), shut down in 80s
Transfer time ≤ 10ms
THDV (resistive load) ≤ 5%
Protections Overload, short circuit (inverter), battery low voltage, battery overcharge, overtemperature
Overload time (mains mode)  120s for 110%, 60s for 125%, 10s for 150% (transfer to bypass mode)
 Overload time (inverter mode) 60s for 110%, 10s for 125%, 5s for 150% (Shut down direcity)
Mute Automatic mute in 60s or by manual

 

Battery capacity 12Vx1 12Vx7Ahx2 12V/9Ahx2 12V/9Ahx3 12V/9Ahx4
Charging current Standard model (S): 1A (defult)
Long time model(H): 10A (defual): <10A, set step 1A; ≥ 10A, set step 5A
Max. 10A (H) Max. 15A (H) / Max. 20A(H) Max. 25A (H)
Equalizing charge voltage Single battery 14.1 VDC (default), 13.6-15VDC adjustable
Floating charge voltage Single battery 13.5 VDC (default), 13.2-14.6VDC adjustable
Low voltage alarm point Single battery 10.8 VDC (default), 9.6-13VDC adjustable
Low voltage shutdown point Single battery 10.2 VDC (default), 9.6-11.5VDC adjustable
Communications          
USB+RJ45 Supports Windows98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8/ 10
SNMP Power management from SNMP manager and web browser (standard with slot)
Other          
Operating temperature 5°C - 40°C
Operating humidity Relative humidity ≤ 93%
Noise level  ≤ 50dB (1m)

 